- Piece/Pieces
- 1
- , Piece/Pieces
- 5500 INR
- 90.0 x 95.0 x 36.0 mm
- OD 10 mm Millimeter (mm)
- White
- Probe 210 mm Millimeter (mm)
- AVT series devices are commonly used in HVAC/R systems
- Digital
- 220 g Grams (g)
- ABS
- 24 VAC or VDC, 10 %
- Velocity: 5% from reading %
- Digital Only
- 0...2 / 0...10 / 0...20 m/s
The AVT series air velocity transmitters are engineered for building automation in the HVAC/R industry. The AVTs measure air velocity and temperature, with field selectable range and output options in a single device. Designed with a duct mount probe and adjustable collar suitable for round or rectangular ducts.
AVT series devices include:
3 field selectable measurement ranges for air velocity, selectable via jumper
Separate readings and outputs for air velocity and temperature.
Proportional output options include: voltage (0-10 V) and current(4-20 mA).
AVT series device options offer:
Backlit display & Field adjustable relay
Field adjustable relay
SPECIFICATIONS
Media Compatibility | Air, non-combustible and non-aggressive gases |
Measuring elements | Temperature: NTC 10k & Velocity: Pt1000 |
Measurement Ranges | Velocity: Range: 0-2 m/s Range: 0-10 m/s Range: 0-20 m/s Temperature: 0-50 DegreeC |
Accuracy | Velocity: Range: 0-2 m/s: less than 0.2 m/s + 5 % reading Range: 0-10 m/s: less than 0.5 m/s + 5 % reading Range: 0-20m/s: less than 1 m/s + 5 % reading Temperature: less than 0.5DegreeC |
Material | ABS |
Environment | 0 to 50Degree C 0 to 95% rH |
Mounting | Flange, D4.0 mm |
Dimension | Case: 90x 95x36 Prode: OD 10mm, length 210 mm |
Display | 3 ý digit LCD backlit display Size: 45.7 x 12.7 mm |
Input | 24 VDC/24VAC+- 10% |
Output | 0 to 10 V 4 to 20mA |
- All India